T510 / T600 series inverter installed with T600ws6 control card can realize the circulation and constant pressure water supply of two pumps driven by one ....
Applicable to T510 / T600 series, one drag two extension wiring
Code |
Setting Value |
Descriptions |
F0.02 |
8 |
PID closed loop operation control valid |
F9.04 |
1.00 |
PID gives maximum feedback range. If the maximum range of remote pressure gauge is 1 MPa, the parameter is set to 1.00, the maximum range of remote pressure gauge is 0.6MPa, and the parameter is set to 0.60. |
F9.36 |
75.0% |
Wake up coefficient (this parameter may not be set if sleep wake-up function is not required) |
F9.37 |
Actual determination |
Wake up delay time (this parameter may not be set if sleep wake-up function is not required) |
F9.38 |
38.00Hz |
Sleep frequency (this parameter may not be set if sleep wake function is not required) |
F9.39 |
Actual determination |
Sleep wake delay time. 0 is invalid for sleep (this parameter may not be set if sleep wake function is not required) |
F9.42 |
2 |
Sleep wake delay 0 is not valid for sleep (this parameter may not be set if sleep wake function is not required) |
F9.43 |
Actual determination (Min.) |
Timing rotation time. 0 is invalid for timed rotation. |
Note: In the monitoring state, the set pressure can be adjusted through the up and down keys of the keyboard. If 0.20 MPa is displayed, the set 2 kg pressure will be indicated |